Worked example

Two 6 AWG and one 10 AWG THHN add up to 0.1225 in². A ½-in EMT has 0.122 in² at 40%. Step up to ¾-in EMT, listed at 0.213 in².

Calculation method

  1. Choose the actual raceway

    Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.

  2. Add every object occupying space

    Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.

  3. Read the area limit

    Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.

The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.

Common questions

Does a wire equipment ground occupy conduit fill?

Yes. Include a wire-type equipment grounding conductor using its occupied area. Chapter 9 fill and the count used for ampacity adjustment serve different purposes.

Why can the result fit slightly above the printed fill percentage?

Table 4 values have their own rounding. Chapter 9 Note 7 also permits the next whole conductor when the equal-area quotient has a fractional part of at least 0.8. The worksheet calls out any use of this allowance.