Worked example
The two large wires occupy 0.1014 in² and the smaller wire adds 0.0211 in². The 0.1225 in² total exceeds the ½-inch EMT 40% allowance of 0.122 in². The ¾-inch allowance is 0.213 in².
The small difference matters because the installation has mixed occupied areas. Use the actual dimensions for a bare EGC if permitted. A listed metal raceway can serve as an equipment ground in some applications. Equipment instructions and bonding requirements govern the actual design.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
Which fill band applies to the 6-6-10 conductor bundle?
Use the 40% column because three objects occupy the raceway, including the grounding conductor.
Could I round 0.1225 in² down for half-inch EMT?
Use the calculated sum against the tabulated capacity. The Note 7 whole-conductor allowance applies to equal-size occupied areas.