Worked example
6 AWG copper starts at 75 A in the 90°C column. At 40°C with six current-carrying conductors, 75 × 0.91 × 0.80 = 54.6 A. The 75°C terminal cap is 65 A, so 54.6 A governs.
Calculation method
Start in the insulation column
Look up the conductor and its 75°C or 90°C insulation ampacity in 310.16. Use the rating marked for the location.
Multiply the correction and adjustment
Apply the 310.15(B)(1) ambient factor and 310.15(C)(1) conductor-count factor. Add 33°C for sun-exposed rooftop raceway or cable below ¾ in in the 2023 edition, with the exception for XHHW-2.
Apply the lower terminal or insulation limit
The allowable result is the lower of the adjusted number and the applicable 310.16 termination cap. Ordinary small-conductor OCPD limits from 240.4(D) are shown separately.
Apply the adopted edition and evaluate the actual route. Neutral counting, single-conductor arrangements and short raceway exceptions require their own conditions.
Common questions
Can a 90°C conductor start at 90°C with 75°C terminals?
Yes, where the conductor is rated for the environment. Use its 90°C value in the correction and adjustment calculation and cap the result at the applicable 75°C ampacity.
Can an XHHW-2 conductor skip the ambient correction on a roof?
XHHW-2 is excepted from the rooftop temperature adder. Use the actual ambient temperature and conductor count for the other factors.