Worked example

At 35°C, 6 AWG aluminum starts at 60 A in the 90°C column. Multiply by 0.96 to get 57.6 A, then apply the 50 A ceiling for 75°C terminations.

Only use the exception with conductors actually marked XHHW-2. Verify wet-location suitability and equipment aluminum ratings. Conduit fill still uses the correct outside area for the product you are pulling.

Calculation method

  1. Start in the insulation column

    Look up the conductor and its 75°C or 90°C insulation ampacity in 310.16. Use the rating marked for the location.

  2. Multiply the correction and adjustment

    Apply the 310.15(B)(1) ambient factor and 310.15(C)(1) conductor-count factor. Add 33°C for sun-exposed rooftop raceway or cable below ¾ in in the 2023 edition, with the exception for XHHW-2.

  3. Apply the lower terminal or insulation limit

    The allowable result is the lower of the adjusted number and the applicable 310.16 termination cap. Ordinary small-conductor OCPD limits from 240.4(D) are shown separately.

Apply the adopted edition and evaluate the actual route. Neutral counting, single-conductor arrangements and short raceway exceptions require their own conditions.

Common questions

Does the XHHW-2 exception raise the 75°C aluminum terminal ampacity?

The 75°C terminal cap is unchanged. In this example it limits the result to 50 A.

Does XHHW-2 need current-carrying conductor adjustment at nine wires?

Use the applicable 70% factor for seven through nine unless a separate exception applies to the installation.