Worked example

At a 35°C outdoor ambient and a half-inch clearance, use 68°C. In the 90°C column the 66–70°C bracket is 0.58. For 6 AWG copper that gives 75 × 0.58 = 43.5 A before other adjustments.

Measure to the bottom of the raceway or cable. At exactly ¾ inch the modeled adder drops out. Check the hottest segment and the actual insulation temperature rating. The earlier ⅞-inch figure comes from prior editions.

Calculation method

  1. Start in the insulation column

    Look up the conductor and its 75°C or 90°C insulation ampacity in 310.16. Use the rating marked for the location.

  2. Multiply the correction and adjustment

    Apply the 310.15(B)(1) ambient factor and 310.15(C)(1) conductor-count factor. Add 33°C for sun-exposed rooftop raceway or cable below ¾ in in the 2023 edition, with the exception for XHHW-2.

  3. Apply the lower terminal or insulation limit

    The allowable result is the lower of the adjusted number and the applicable 310.16 termination cap. Ordinary small-conductor OCPD limits from 240.4(D) are shown separately.

Apply the adopted edition and evaluate the actual route. Neutral counting, single-conductor arrangements and short raceway exceptions require their own conditions.

Common questions

Is ⅞ inch still the Chapter 3 threshold in 2023?

The 2023 threshold is ¾ inch, or 19 mm. Confirm the locally adopted edition when comparing older designs.

What changes if the raceway has no direct rooftop sun?

Use the actual ambient for the correction in this worksheet when the direct-sun rooftop condition does not apply.