Worked example

At 30°C with three current-carrying conductors, the adjustment and correction both equal 1.00. NEC 310.16 gives 40 A at 90°C and 35 A at 75°C. NEC 240.4(D) then sets the usual maximum OCPD at 30 A.

The thermal rating and overcurrent device limit answer different questions. Review any specific rules for motors, HVAC or other equipment separately. For common branch-circuit wiring, choose the breaker and conductor with the ordinary small-conductor limit in mind.

Calculation method

  1. Start in the insulation column

    Look up the conductor and its 75°C or 90°C insulation ampacity in 310.16. Use the rating marked for the location.

  2. Multiply the correction and adjustment

    Apply the 310.15(B)(1) ambient factor and 310.15(C)(1) conductor-count factor. Add 33°C for sun-exposed rooftop raceway or cable below ¾ in in the 2023 edition, with the exception for XHHW-2.

  3. Apply the lower terminal or insulation limit

    The allowable result is the lower of the adjusted number and the applicable 310.16 termination cap. Ordinary small-conductor OCPD limits from 240.4(D) are shown separately.

Apply the adopted edition and evaluate the actual route. Neutral counting, single-conductor arrangements and short raceway exceptions require their own conditions.

Common questions

Can I use the 40 A insulation rating to pick a 40 A breaker for #10 copper?

The ordinary small-conductor protection ceiling is 30 A. Look for a specific code allowance before considering a different application.

What is the ordinary small-conductor limit for 10 AWG aluminum?

The modeled general protection limit for 10 AWG aluminum or copper-clad aluminum is 25 A under 240.4(D).