Worked example

10 AWG copper has a 40 A base in the 90°C column. At 30°C, nine conductors give 28 A after grouping and ten give 20 A. Both results are below the 35 A 75°C terminal cap.

A neutral carrying only the unbalanced portion of the other conductors can be excluded under the applicable section. Neutrals of certain wye circuits and major nonlinear load configurations can count. Equipment grounding and bonding conductors are excluded from this count.

Calculation method

  1. Start in the insulation column

    Look up the conductor and its 75°C or 90°C insulation ampacity in 310.16. Use the rating marked for the location.

  2. Multiply the correction and adjustment

    Apply the 310.15(B)(1) ambient factor and 310.15(C)(1) conductor-count factor. Add 33°C for sun-exposed rooftop raceway or cable below ¾ in in the 2023 edition, with the exception for XHHW-2.

  3. Apply the lower terminal or insulation limit

    The allowable result is the lower of the adjusted number and the applicable 310.16 termination cap. Ordinary small-conductor OCPD limits from 240.4(D) are shown separately.

Apply the adopted edition and evaluate the actual route. Neutral counting, single-conductor arrangements and short raceway exceptions require their own conditions.

Common questions

Is ten physically installed wires always ten current-carrying conductors?

Count the current-carrying conductors under 310.15(E). For example, a wire equipment ground takes physical space and has no normal load current.

Can I split the example into multiple conduits to change the adjustment?

Evaluate each raceway or cable grouping as installed and any bundling rules that apply. Fewer current-carrying wires in a group can improve ampacity.