Worked example

With 6 AWG copper in PVC, 48 A over 150 ft at unity PF gives 2 × 48 × 0.150 × 0.49 = 7.056 V, or 2.94% at 240 V.

Calculation method

  1. Enter one-way length and operating current

    The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.

  2. Account for power factor

    Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.

  3. Size for both voltage and temperature

    The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.

Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.

Common questions

Why does a three-phase run use √3 instead of 2?

For an evenly loaded three-phase system, the phase-to-phase phasor difference produces the √3 multiplier. A two-wire single-phase loop uses the out-and-back multiplier of 2.

Can the calculator report voltage rise?

Yes. A leading power factor can make the reactive component larger than the resistive drop. A negative voltage change represents rise in this approximate model.