Worked example
Combine 0.49 × 0.90 plus 0.051 × √(1 − 0.90²) to get roughly 0.463 Ω per 1,000 ft. Multiply by √3 × 60 × 0.150 for 7.22 V, about 3.47% of 208 V.
The entered voltage is 208 V line to line. A separate 120 V single-phase load on the same system uses a two-wire loop and the voltage between its hot and neutral. Treat an unbalanced system with a circuit-specific model.
Calculation method
Enter one-way length and operating current
The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.
Account for power factor
Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.
Size for both voltage and temperature
The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.
Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.
Common questions
Which 208 V three-phase conductor meets 3% in this preset?
The 4 AWG copper comparison is below 3% with these inputs and meets the basic ampacity screen.
Why does lagging power factor add reactance to the 208 V result?
The estimate projects the impedance onto the load voltage. The projected inductive term is positive for lagging current.