Worked example
For 12 AWG use 2.0 Ω per 1,000 ft. The formula is 2 × 12 × 0.100 × 2.0 = 4.8 V, or 4%. For 10 AWG use 1.2 Ω per 1,000 ft, giving 2.4%.
When the source is 120 V, a small absolute drop uses more of the percentage budget than it does at 240 V. Check the upstream feeder and the load’s minimum voltage when choosing a branch target.
Calculation method
Enter one-way length and operating current
The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.
Account for power factor
Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.
Size for both voltage and temperature
The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.
Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.
Common questions
Do I enter 200 ft to represent the two conductors in a 100 ft circuit?
Enter 100 ft. The single-phase formula already includes both paths.
Which size meets a 3% target for this 120 V branch?
In this preset, 10 AWG copper is the smallest supported conductor meeting both the voltage drop and the baseline ampacity screen.