Worked example
The single-phase model uses the 277 V line-to-neutral voltage and the two-wire loop. The estimated drops are 4.04% and 2.43%. With a 20 A continuous load, the conductor design screen also checks 25 A.
A 277 V lighting load often sits on a 480Y/277 V system. Check the luminaire input range, power factor, shared-neutral harmonic current and actual breaker requirements. Select the hottest route conditions in the derating tool.
Calculation method
Enter one-way length and operating current
The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.
Account for power factor
Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.
Size for both voltage and temperature
The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.
Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.
Common questions
Do I enter 480 V for one 277 V lighting branch?
Enter 277 V for a load connected line to neutral. A balanced 480 V three-phase load is a different circuit.
How much of the 277 V 3% drop budget is 11.2 V?
Three percent is 8.31 V, so the 12 AWG example exceeds it by about 2.89 V.