Worked example
With 75°C terminals, a 100 A feeder has a base result of 3 AWG copper or 1 AWG aluminum. At 100 A and 200 ft in PVC, both base sizes drop about 10 V. A 3% target moves the estimate to 1 AWG copper or 2/0 AWG aluminum.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
Can a ground rod replace the equipment ground on a detached feeder?
Run an EGC with the modern four-wire feeder. A grounding electrode system at the building serves a different function under 250.32 and is bonded to the equipment grounding system.
Is aluminum SER suitable in a buried PVC feeder?
NEC 338.12(A)(2) excludes Type SE cable underground, including in conduit. Consider listed wet-location individual conductors or a listed direct-burial wiring method.