Worked example
A 120 A continuous load gives a 150 A design value. The 3/0 aluminum wire is rated 155 A at 75°C. At 120 A and 125 ft, the PVC-based voltage drop is about 3.9 V at unity PF.
Confirm both lugs are listed for aluminum, the conductor range matches 3/0, and the route has its actual ampacity corrections. A feeder serving a workshop or the loads of one subpanel uses ordinary ampacity planning in this example.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
What is the corresponding 150 A copper feeder floor?
At 75°C, 1/0 copper is rated 150 A under Table 310.16, before correction and adjustment.
Does the 3/0 aluminum insulation column stay at 175 A in this feeder?
The 90°C rating can be used for corrections when applicable. The 75°C terminal cap leaves 155 A before other constraints.