Worked example
At verified 75°C terminals, the 310.16 ampacity floors are 3 AWG Cu and 1 AWG Al. Each is about 0.25 Ω per 1,000 ft in PVC. The 400 ft loop at 100 A drops about 10 V, above the 7.2 V target.
Compare the loaded conductor runs and terminal acceptance before pricing. A 120 V leg can consume a larger share of its voltage allowance. An upsize for voltage drop can also require a larger wire-type ground under 250.122(B).
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
What drop does 2/0 aluminum give at 200 ft and 100 A?
Using 0.16 Ω per 1,000 ft at unity PF, the estimate is 6.4 V or 2.67% at 240 V.
Can I apply the residential 83% sizing rule to a detached garage?
Ordinary garage feeders generally supply only part of the dwelling load. Use the general ampacity method unless the entire-dwelling conditions are met.