Worked example
The copper wire is rated 130 A at 75°C and gives about 4.5 V drop at the modeled 100 A load over 150 ft. 2/0 aluminum is rated 135 A and drops about 4.8 V in PVC.
Large shop loads can include welders, air compressors and motors with their own calculation rules. Use a calculated feeder load and check starting voltage separately. The table assumes a single set of conductors with ordinary supply protection.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
Why is 1/0 aluminum insufficient for full 125 A feeder sizing?
Its 75°C ampacity is 120 A. This preset sizes to the full breaker rating and leaves use of 240.4(B) as a separately verified option.
Does a breaker rating set the current for voltage drop?
Use the anticipated operating line current. The feeder protective rating affects conductor and EGC checks.