Worked example
The 4/0 aluminum 75°C ampacity is 180 A. 250 kcmil aluminum reaches 205 A, and at 160 A over 200 ft its estimated drop in PVC is 5.44 V. The 160 A continuous component calls for a 200 A sizing load.
NEC 310.12 can allow different sizes for qualified whole-dwelling supplies. NEC 240.4(B) also has a limited next-size provision, but it cannot cure a conductor that falls below the calculated load in this example. Verify the actual use case before ordering cable.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
Does 4/0 aluminum always fail on a 200 A breaker?
Specific whole-dwelling or next-size rules can apply when all conditions are met. Check conductor ampacity against the calculated load and installation.
Can a 200 A shop feeder use 2/0 copper under the ordinary table?
2/0 copper is rated 175 A at 75°C. The full-rating ordinary copper starting point is 3/0 at 200 A.