Worked example

At 48 A continuous, the feeder design load is 60 A. For 6 AWG copper over 100 ft at 240 V, expect roughly 4.70 V or 1.96% drop under the PVC approximation.

Verify a four-wire feeder and an insulated neutral isolated from the equipment grounding enclosure. The detached building generally needs a grounding electrode system and a building disconnect. Evaluate mixed 120/240 V loads on the most heavily loaded leg.

Calculation method

  1. Calculate the actual feeder load

    Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.

  2. Compare the wire options

    Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.

  3. Plan the grounding and disconnect

    A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.

The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.

Common questions

What is the 60 A garage feeder equipment-ground baseline?

Table 250.122 starts at 10 AWG copper or 8 AWG aluminum. The installed conductor system and any voltage-drop upsize affect the final choice.

What happens if the garage breaker has 60°C terminals?

Select 60°C to recalculate. The 6 AWG copper value drops to 55 A, below the full 60 A design in this example.