Worked example
For an above-grade dry Type SER example at 75°C, 1 AWG aluminum reaches 100 A and drops about 4 V at 80 A over 100 ft using the underlying PVC impedance approximation. The actual assembly has its own neutral and ground sizes.
Type SE is excluded underground even inside a raceway. XHHW-2 singles can serve in a suitable wet raceway. Listed direct-burial MHF can serve a permitted exterior route. Look for the appropriate individual conductor markings before using them in any interior portion.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
Can I transition from wet-location MHF to an indoor section?
Verify the conductor marking and wiring method at the transition. USE-only marking is insufficient for interior wiring.
Does SER and MHF of the same phase gauge have the same EGC?
Cable assemblies can use different EGC and neutral sizes. Check the specific cable construction against the design.