Worked example
The 70 A operating example includes 40 A continuous, giving an 80 A design load. At 75°C with copper, start with 4 AWG. A 30 A standalone 120 V leg with equal-size line and neutral drops an estimated 1.67 V over 90 ft.
Check the building disconnect location and rating under Article 225. Keep the feeder neutral isolated from the enclosure downstream. Bond the equipment grounding system and electrodes per Article 250, using the required electrode and grounding-electrode-conductor design.
Calculation method
Calculate the actual feeder load
Enter line current and the continuous portion. The feeder design value adds 25% of the continuous portion. Select an upstream breaker that covers the calculated load.
Compare the wire options
Find a 310.16 ampacity floor and check voltage drop at the operating current. For cable assemblies the selected Table 9 raceway represents an impedance approximation. Confirm the actual product, neutral and EGC sizes.
Plan the grounding and disconnect
A modern detached feeder generally includes two hots, an insulated neutral and an equipment ground. Check the building disconnect and grounding electrode system at the detached structure separately.
The model uses ordinary feeder sizing. NEC 310.12 is specific to qualifying feeders supplying an entire dwelling load. This worksheet conservatively requires the derated wire to carry the design load, then applies the breaker setting and selected 240.4(B) option.
Common questions
Should the feeder neutral and ground share a bar at the detached building?
For a modern four-wire feeder, keep the insulated neutral isolated downstream and bond the equipment grounding bar as required.
How many rods does the detached shop need?
Inspect all electrodes present and evaluate the applicable electrode rule. A single rod can require a supplemental electrode unless its resistance to earth meets the applicable exception.