Worked example

Table 9 values for this case are 0.25 Ω resistance and 0.059 Ω reactance per 1,000 ft. Multiply √3 × 100 × 0.300 by 0.25 × 0.85 + 0.059 × √(1 − 0.85²) to get about 2.64%.

For a motor, evaluate starting voltage and Article 430 conductor and protective-device requirements separately. A running-current estimate helps compare routes, while the motor’s specified current and the installation design control their own checks.

Calculation method

  1. Enter one-way length and operating current

    The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.

  2. Account for power factor

    Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.

  3. Size for both voltage and temperature

    The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.

Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.

Common questions

Can I use this running drop as the motor-start drop?

Use separate starting current and power factor data, and account for source impedance and the starting method.

Does steel raceway affect the 480 V motor calculation?

Select steel to use the Table 9 values for that geometry. The reactance for 3 AWG is higher in steel than in PVC.