Worked example

For the 100 ft example, 40 A steady draw over the 240 V loop gives about 3.92 V of drop with 6 AWG copper. The same current on a standalone 120 V leg and equal-size neutral uses twice the percentage budget.

For a home garage or outdoor receptacle, check NEC 210.8(A) and local amendments. A qualifying RV-park pedestal can have different 551.71(F) treatment. Verify the particular location and RV supply equipment with the inspector. The worksheet models drop only, using a 40 A continuous scenario to screen a 50 A wire floor.

Calculation method

  1. Enter one-way length and operating current

    The formula applies a multiplier of 2 for the single-phase loop or √3 for balanced three-phase, using one-way feet divided by 1,000.

  2. Account for power factor

    Use ΔV = multiplier × I × L × (R cos φ + X sin φ). Table 9 supplies R and X at 75°C and 60 Hz. The reactive term changes sign for leading power factor.

  3. Size for both voltage and temperature

    The comparison finds the first supported conductor that meets the selected target and the unadjusted 310.16 ampacity screen with the small-conductor limits. Apply actual ambient, bundling and equipment limits before specifying a wire.

Chapter 9 Table 9 is based on three single conductors in raceway. A two-wire or cable assembly uses the values as an estimate. For a long run with a large predicted change, use an engineered load-flow model.

Common questions

Can I omit the neutral for a 50 A RV receptacle used at home?

An RV 14-50 provides a neutral for its 120 V loads in addition to the two hot legs and equipment ground.

Is a home RV outlet covered by the RV-park GFCI treatment?

The potential Article 551 exception has site conditions. Check the dwelling-location GFCI rule and the locally adopted text for a home outlet.