Worked example
At 40%, the respective areas are 0.213 and 0.346 in². Divide by 0.0507 in² per wire to get 4.20 and 6.82. The 0.82 fraction qualifies for same-size rounding in the 1-inch example.
The seven-wire result applies to the identical cross-sectional areas in this example. If the pull includes different wire sizes, add their areas and compare directly to Table 4. Consider the jamming risk when several conductors have similar diameters.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
Why does seven 6 AWG in 1-inch EMT show slightly more than 40%?
The physical area is 0.3549 in². Chapter 9 Note 7 supports the count through the equal-area calculation, which the worksheet explicitly identifies.
Do five 6 AWG THHN fit in ¾-inch EMT?
Five occupy 0.2535 in². The available area and equal-size quotient both fall short for ¾-inch EMT.