Worked example
Each 10 AWG THHN takes 0.0211 in². Five add up to 0.1055 in² against the 0.122 in² Table 4 limit. Six occupy 0.1266 in² and the equal-size quotient of 5.78 falls short of the Note 7 rounding threshold.
Start with the insulated area of the actual wire. If the fifth wire is an insulated EGC, it still occupies space. For a bare or compact wire, enter its occupied area separately. A wire count within the fill limit can still require ampacity adjustment when several conductors carry load.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
Would one extra 10 AWG THHN fit in ½-inch EMT?
A sixth wire exceeds the 0.122 in² allowance. The five-to-six rounding exception requires a quotient of at least 5.8.
Is the 10 AWG half-inch estimate the same for XHHW-2?
The 10 AWG XHHW-2 area is 0.0243 in². Recalculate with that insulation type because it uses a different Table 5 value.