Worked example

A 48 A Tesla Gen 3 setting yields a 60 A circuit. At 30°C with 75°C terminals and two current-carrying conductors, 6 AWG copper THWN-2 has a 65 A terminal-limited rating. A 75 ft run gives about 3.53 V drop at 48 A.

Calculation method

  1. Start with the current the EVSE can draw

    Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.

  2. Check the weakest temperature rating

    Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.

  3. Check the operating drop and ground

    Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).

Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.

Common questions

What does the 125% factor apply to on a Level 2 charger?

It applies to the continuous charging load for branch-circuit protection. A 48 A setting yields 60 A; a 32 A setting yields 40 A.

Will an 80 A ChargePoint breaker provide 80 A charging?

The CPH50 Home Flex tops out at 50 A charging. Some documentation lists a hardwired 80 A circuit as an option. Match the exact installation guide and wire terminals on the equipment.