Worked example
With 75°C terminals, 8 AWG copper THWN-2 has 50 A of tabulated ampacity. The 60°C NM-B column gives only 40 A for the same gauge, so the dry cable comparison starts at 6 AWG copper.
Use a listed receptacle suitable for the application, verify the device instructions, and account for temperature and conductor grouping. The 14-50 has two hots, a neutral and equipment grounding. An EVSE receptacle needs GFCI in the Article 625 check.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
Does a 50 A receptacle mean 50 A of continuous EV charging?
At the ordinary 125% sizing factor, a 50 A circuit can provide up to 40 A of continuous charging where the EVSE listing permits it.
Why does the result use a different NM-B gauge for the same charger?
The 60°C ampacity cap on NM-B changes the current limit for each gauge, even with 75°C devices at both ends.