Worked example
A 75°C-rated termination can use up to 65 A for 6 AWG copper THWN-2 before site correction. The NM-B screen moves to the next supported ampacity size. Verify that an approved cable is available and its conductor fits the charger.
The NM-B insulation marking can support thermal adjustment under the cable rule, and the final allowable current still has the 60°C cap. Next-size overcurrent protection requires the conductor to carry the actual calculated design load.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
Can the next-size rule make 55 A NM-B carry a 60 A sizing load?
The required conductor ampacity remains 60 A in this example. The next-size rule governs selection of an overcurrent protector under stated conditions.
Does #6 wire always mean the same EV branch capacity?
Check insulation, cable type, the weakest termination and site factors. The same copper area can have 55 A at 60°C or 65 A at 75°C.