Worked example

If general loads total 35,000 VA, the demand subtotal is 20,000 VA. Add a 7,750 VA governing heat-pump case for 27,750 VA, or 115.63 A at 240 V before EVSE.

Calculation method

  1. Build the connected general load

    Use 3 VA per qualifying square foot, 1,500 VA per small-appliance or laundry circuit, and relevant nameplate values. Take the first 10,000 VA at full value and 40% of the rest.

  2. Compare HVAC operating cases

    Use the largest applicable 220.82(C) case. For a heat pump, use the compressor at 100% and the supplemental electric heat at 65%, with interlocked stages compared separately. Separately controlled electric heat uses 65% for one to three units or 40% for four or more.

  3. Add EVSE and divide by voltage

    This worksheet adds a conservative EVSE allowance outside the 40% band, using at least 7,200 VA per unit or its higher nameplate as a planning assumption. Confirm with the authority having jurisdiction how to include EVSE under the locally adopted optional method.

NEC 220.82 applies to a qualifying individual dwelling on a single 120/240 V or 208Y/120 V three-wire set with ampacity of 100 A or greater. Existing-dwelling and measured-load methods, approved load management, utility metering and service equipment ratings require separate review.

Common questions

Does a 100 A dwelling service always have room for a charger?

Use the calculated load and a verified EVSE rating or approved management strategy. A panel may have open breaker positions without spare service ampacity.

How much of an electric heat strip is counted under 220.82?

For supplemental heat with a heat pump, this worksheet applies 65% to the strips. A documented interlock determines whether that result is added to the compressor or compared with it.