Worked example

The first 10 kVA plus 40% of 40 kVA gives 26 kVA of general demand. Heating is 7 kVA of compressor plus 6.5 kVA of demand from 10 kVA of supplemental heat. Add 8.5 kVA of EVSE allowance.

This is a boundary example. Check whether the compressor and strips can run together and whether another HVAC operating case is larger. Look at an approved load-managed EVSE option only with a documented control and local confirmation.

Calculation method

  1. Build the connected general load

    Use 3 VA per qualifying square foot, 1,500 VA per small-appliance or laundry circuit, and relevant nameplate values. Take the first 10,000 VA at full value and 40% of the rest.

  2. Compare HVAC operating cases

    Use the largest applicable 220.82(C) case. For a heat pump, use the compressor at 100% and the supplemental electric heat at 65%, with interlocked stages compared separately. Separately controlled electric heat uses 65% for one to three units or 40% for four or more.

  3. Add EVSE and divide by voltage

    This worksheet adds a conservative EVSE allowance outside the 40% band, using at least 7,200 VA per unit or its higher nameplate as a planning assumption. Confirm with the authority having jurisdiction how to include EVSE under the locally adopted optional method.

NEC 220.82 applies to a qualifying individual dwelling on a single 120/240 V or 208Y/120 V three-wire set with ampacity of 100 A or greater. Existing-dwelling and measured-load methods, approved load management, utility metering and service equipment ratings require separate review.

Common questions

What heat-pump demand is counted in the 200 A example?

13.5 kVA, consisting of the full 7 kVA compressor plus 65% of the 10 kVA supplemental heat.

What if a larger EVSE raises the computed demand above 48 kVA?

The modeled load exceeds 200 A at 240 V. Reevaluate actual nameplates, control options, and the service tiers available for the site.

References