Worked example
3,600 VA of floor-area load and 4,500 VA of kitchen and laundry circuits combine with 15,000 VA of appliances. Take the first 10,000 VA plus 40% of 13,100 VA for 15,240 VA. Add 3,500 VA of cooling.
The worksheet assumes the example nameplates and only one governing HVAC operating case. If the project adds an EVSE, electric water heating, or a heat pump, enter those actual nameplates before comparing the 100 A service.
Calculation method
Build the connected general load
Use 3 VA per qualifying square foot, 1,500 VA per small-appliance or laundry circuit, and relevant nameplate values. Take the first 10,000 VA at full value and 40% of the rest.
Compare HVAC operating cases
Use the largest applicable 220.82(C) case. For a heat pump, use the compressor at 100% and the supplemental electric heat at 65%, with interlocked stages compared separately. Separately controlled electric heat uses 65% for one to three units or 40% for four or more.
Add EVSE and divide by voltage
This worksheet adds a conservative EVSE allowance outside the 40% band, using at least 7,200 VA per unit or its higher nameplate as a planning assumption. Confirm with the authority having jurisdiction how to include EVSE under the locally adopted optional method.
NEC 220.82 applies to a qualifying individual dwelling on a single 120/240 V or 208Y/120 V three-wire set with ampacity of 100 A or greater. Existing-dwelling and measured-load methods, approved load management, utility metering and service equipment ratings require separate review.
Common questions
How many kitchen and laundry circuits are in the small-home example?
Two 20 A small-appliance circuits and one 20 A laundry circuit contribute 4,500 VA under the optional method.
How much spare calculated capacity remains in this 100 A example?
About 21.9 A at 240 V before any project changes, under the entered assumptions. Check the actual connected equipment.