Worked example
This example has 36,000 VA of general load. Take 10,000 VA at full value plus 10,400 VA as the remainder contribution, then add 8,400 VA of cooling. The 125 A comparison leaves 5 A of calculated room.
Service ratings reflect approved equipment and utility standards. A 150 A option can add future capacity where equipment is available. Check the governing HVAC and any planned EVSE before selecting a tier.
Calculation method
Build the connected general load
Use 3 VA per qualifying square foot, 1,500 VA per small-appliance or laundry circuit, and relevant nameplate values. Take the first 10,000 VA at full value and 40% of the rest.
Compare HVAC operating cases
Use the largest applicable 220.82(C) case. For a heat pump, use the compressor at 100% and the supplemental electric heat at 65%, with interlocked stages compared separately. Separately controlled electric heat uses 65% for one to three units or 40% for four or more.
Add EVSE and divide by voltage
This worksheet adds a conservative EVSE allowance outside the 40% band, using at least 7,200 VA per unit or its higher nameplate as a planning assumption. Confirm with the authority having jurisdiction how to include EVSE under the locally adopted optional method.
NEC 220.82 applies to a qualifying individual dwelling on a single 120/240 V or 208Y/120 V three-wire set with ampacity of 100 A or greater. Existing-dwelling and measured-load methods, approved load management, utility metering and service equipment ratings require separate review.
Common questions
Is 120 A a calculated load or a normal service tier?
Here it is the calculated current. The worksheet compares supported nominal tiers, including 125 A and 150 A.
How does 208Y/120 V change the 28.8 kVA example?
For a dwelling on a single 208Y/120 V three-wire set with the same total VA, divide by 208 V. The estimate is about 138.5 A.