Worked example
Connected general load is 90 kVA, producing 42 kVA demand. Two 11.52 kVA EVSEs add 23.04 kVA and the governing heating case is 15 + 0.65 × 20 = 28 kVA.
A 400 A service label and the continuous rating of a specific meter socket or grouped disconnect assembly are distinct equipment values. Check the utility service guide, service configuration and eligible calculation method before any equipment selection.
Calculation method
Build the connected general load
Use 3 VA per qualifying square foot, 1,500 VA per small-appliance or laundry circuit, and relevant nameplate values. Take the first 10,000 VA at full value and 40% of the rest.
Compare HVAC operating cases
Use the largest applicable 220.82(C) case. For a heat pump, use the compressor at 100% and the supplemental electric heat at 65%, with interlocked stages compared separately. Separately controlled electric heat uses 65% for one to three units or 40% for four or more.
Add EVSE and divide by voltage
This worksheet adds a conservative EVSE allowance outside the 40% band, using at least 7,200 VA per unit or its higher nameplate as a planning assumption. Confirm with the authority having jurisdiction how to include EVSE under the locally adopted optional method.
NEC 220.82 applies to a qualifying individual dwelling on a single 120/240 V or 208Y/120 V three-wire set with ampacity of 100 A or greater. Existing-dwelling and measured-load methods, approved load management, utility metering and service equipment ratings require separate review.
Common questions
Why is the two-EVSE allowance 23.04 kVA in the large-home example?
Each identical unit’s entered 11.52 kVA nameplate exceeds the 7.2 kVA floor. This project screen counts both.
What if the load is higher than the 400 A tier?
The worksheet reports the computed load and flags it as beyond the supported equipment tiers. The service layout needs a project-specific review.