Worked example
The sizing load is 48 × 1.25 = 60 A. The 75°C 6 AWG copper allowance is 65 A before site factors. With two 6 AWG and one insulated 10 AWG copper ground, the 0.1225 in² sum calls for ¾-inch EMT in the standard fill check.
Check the marked terminals, maximum conductor range, actual ground type, and wet rating. Tesla specifies 4 AWG copper THWN-2 at maximum output for a 60°C breaker. The Tesla wirebox accepts copper final terminations. Choose the outlet entry and fitting to match the manual.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
What ground size does the 60 A Tesla example start with?
Table 250.122 starts a 60 A circuit at 10 AWG copper for a wire-type EGC. Upsized hots can require a proportionately larger EGC.
How far can the Tesla 6 AWG run go at 48 A?
In the unity-PF PVC impedance estimate, about 153 ft one way reaches 3% at 240 V. Confirm the actual circuit and terminal limits.