Worked example
The worked 70 A option with 75°C terminals uses 6 AWG copper at 65 A only if 240.4(B) is applicable. A circuit designed to carry the full breaker rating needs a larger conductor or a reviewed wiring transition because the CPH50 field terminal accepts at most 6 AWG.
ChargePoint literature describes hardwired configurations up to 80 A. Verify the specific hardware instructions, circuit rating and activation setting. Use the breaker override to compare the modeled 80 A case. The maximum EVSE output stays at 50 A.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
Why does 50 A output calculate to a 70 A breaker?
62.5 A is above 60 A and below the next ordinary breaker size of 70 A. Use a pairing permitted by the equipment manual.
What if the wire required for Home Flex is larger than the terminal?
Have the final connection and any listed junction or transition arrangement reviewed for the specific equipment. The calculator flags the terminal limit.