Worked example
In the dry-route preset at 30°C, 8 AWG copper NM-B is the first supported size. Over 60 ft of one-way length the Table 9 estimate gives 3.0 V drop at 240 V.
A generic 40 A circuit result assumes equipment approved for that connection. When the equipment uses a NEMA 14-50 or 6-50 plug, confirm both the listed charging setting and the required receptacle GFCI. Size circuit wiring using the weakest terminal and applicable cable rules.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
Does 10 AWG copper work for a 40 A EV outlet?
Ordinary 10 AWG copper branch-circuit protection is limited to 30 A under 240.4(D). The 32 A charging example uses a 40 A circuit.
Can I use the 32 A preset for hardwired and plug-in EVSE?
The design current is the same. Verify the specific charger permits the installed configuration and the plug-in setting.