Worked example
At the 40 A setting both plug types use a 50 A circuit. In the 75°C copper raceway example, 8 AWG is the ampacity starting point. The EGC is sized independently of the presence of a neutral.
Match the charger plug, the installed receptacle, its terminals, GFCI and environment. The 14-50 route includes the neutral because the receptacle configuration provides one. A hardwired configuration avoids using a receptacle and has its own installation instructions.
Calculation method
Start with the current the EVSE can draw
Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.
Check the weakest temperature rating
Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.
Check the operating drop and ground
Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).
Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.
Common questions
Do both plug types need an equipment grounding conductor?
Both are grounding receptacles. The 6-50 has two hots and ground, while the 14-50 adds a neutral.
Do EVSE receptacles require GFCI in the NEC 2023 calculation scope?
Yes. Section 625.54 applies to receptacles installed for EVSE connection. Check the adopted local rules.