Worked example

With two current-carrying conductors, 30°C ambient and verified 75°C terminations, 3 AWG copper starts at 100 A. At 100 ft and 80 A, the PVC-based unity-PF estimate gives a 4.0 V drop.

Confirm the manufacturer accepts the breaker and termination sizes before considering aluminum upstream. Article 625.43 requires a disconnect review for fixed-in-place equipment rated over 60 A. Verify service capacity for the 19.2 kW charging load at 240 V.

Calculation method

  1. Start with the current the EVSE can draw

    Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.

  2. Check the weakest temperature rating

    Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.

  3. Check the operating drop and ground

    Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).

Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.

Common questions

Which Table 250.122 EGC starts a 100 A EV circuit?

The base sizes are 8 AWG copper or 6 AWG aluminum. Verify any proportional increase for voltage-drop upsizing and all termination restrictions.

How much charging power does 80 A yield at 240 V?

The nominal voltage-current product is 19.2 kVA, about 19.2 kW at unity power factor.