Worked example

The nominal charging power is 6.66 kW at unity PF. Over a 100 ft run, 8 AWG copper in the Table 9 PVC estimate drops 4.99 V, about 2.4% of 208 V.

A line-to-line EVSE on two legs of a 208Y/120 V system is a single-phase load for this voltage-drop model. Have the service loading and equipment compatibility checked. For several charging stations, plan phase loading and managed demand under the applicable site rules.

Calculation method

  1. Start with the current the EVSE can draw

    Multiply the maximum configured charging current by 1.25 and select the smallest supported standard breaker at or above that value. A documented equipment listing can require a specific pairing.

  2. Check the weakest temperature rating

    Select the lowest terminal temperature. Copper NM-B remains limited to the 60°C ampacity in 334.80. The worksheet applies correction and adjustment from the 90°C insulation column of the supported conductors.

  3. Check the operating drop and ground

    Estimate drop at actual charging current using Chapter 9 Table 9 PVC values at unity power factor. The wire-type EGC starts at Table 250.122 and is evaluated for proportional upsizing under 250.122(B).

Check the service load, the installed breaker listing, and the terminal wire range with a qualified electrician. The ampacity screen conservatively applies the design-load floor after derating. Receptacle circuits supplying EVSE require GFCI under 625.54.

Common questions

Does reducing the supply voltage from 240 V change a 32 A sizing load?

At the same configured 32 A, the 125% design current remains 40 A. Voltage changes the power and the drop percentage.

Can I use the three-phase formula on a two-leg 208 V EVSE?

Use the single-phase loop for one line-to-line charger. The balanced three-phase formula applies to a load spread over all three phases.

References