Worked example
Divide 0.213 by 0.0211 to get about 10.09 conductors. The next whole unit would be eleven, and that fraction is below the Note 7 threshold. The working example uses all ten positions.
A circuit may have two or three current-carrying wires plus an EGC. Add up the physical wires first, then count the current-carrying ones for ampacity. A tightly filled pull can warrant a larger trade size for installation even if the area check fits.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
What is the leftover area after ten 10 AWG wires in ¾-inch EMT?
The tabulated area difference is 0.002 in². Another 10 AWG THHN would occupy 0.0211 in².
If I remove a load from the ¾-inch raceway, does fill change?
The physical conductor must be removed for its occupied area to stop counting. Check ampacity independently for the conductors that remain energized.