Worked example
The ¾-inch EMT 40% allowance is 0.213 in². At 0.0437 in² each the XHHW-2 quotient is 4.87, so Note 7 allows five identical XHHW-2 wires. At 0.0366 in² each the THHN quotient is 5.82, so six identical THHN wires can qualify.
The larger area of the XHHW-2 wire in this gauge affects the pull. Use the area corresponding to the product you have, including its actual compact construction where applicable. Check the count adjustment separately for energized wires.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
Does equal ampacity mean equal conduit fill for 8 AWG?
The fill area includes insulation, so two wires with the same metal size and temperature capability can occupy different areas.
Can common 8 AWG THHN and XHHW-2 be counted as one equal-size group?
Use their individual areas. Their nominal AWG matches, but the occupied areas differ.