Worked example
Two wires use 0.1180 in². The 31% column lists 0.097 in² for ½-inch LFNC-B and 0.168 in² for ¾-inch. The ¾-inch size accepts the pair in this case.
Check the conduit label for the exact LFNC construction. The appropriate wire-type EGC in nonmetallic raceway can change the physical count to three and move the calculation to the 40% column. Reenter the ground as a third conductor to see the new outcome.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
Does Type B liquidtight use the same inside area as EMT?
Use the Table 4 dimensions for LFNC-B. EMT, LFNC-A and LFNC-B have independent table entries.
Will a third wire always force a larger liquidtight trade size?
A third wire adds its area and also changes the applicable limit from 31% to 40%. Check the complete set of conductors.