Worked example
The XHHW-2 subtotal is 3 × 0.0814 = 0.2442 in². Adding 0.0366 in² gives 0.2808 in². ¾-inch EMT allows 0.213 in² at 40%, while 1-inch allows 0.346 in².
Confirm the feeder or branch design sets the EGC size before estimating fill. If the actual equipment grounding wire is bare, use its bare occupied area. The dimensions of a listed compact aluminum conductor can also differ from the noncompact Table 5 preset.
Calculation method
Choose the actual raceway
Start with the type printed on the raceway. Schedule 40, Schedule 80, EMT and liquidtight of the same trade size have different inside areas.
Add every object occupying space
Use a separate row for each size or insulation. Use actual area for bare grounds, compact aluminum or dimensions that differ from the Table 5 entries.
Read the area limit
Chapter 9 Table 1 assigns 53% to one conductor, 31% to two, and 40% to three or more. The worksheet uses the tabulated in² limits and identifies the same-size rounding allowance in Note 7.
The graphic uses area-scaled circle placement as an illustration. Bends, pulling tension, conductor jamming, ampacity adjustment, short-nipple rules and the suitability of the raceway are separate design checks.
Common questions
How many current-carrying wires are in a 4-4-4-8 pull?
The EGC counts for fill. Determine whether each of the other three conductors carries normal load under 310.15(E).
Will ¾-inch EMT pass if I use a smaller ground for the 4 AWG pull?
Three 4 AWG XHHW-2 wires alone already occupy 0.2442 in², exceeding the 0.213 in² allowance at 40%.