Worked example
Eleven IQ8M units at 1.35 A give 14.85 A continuous, or 18.56 A at 125%. Two such branches give 29.70 A combined continuous current and a 40 A minimum standard output breaker.
Calculation method
Use AC continuous current per microinverter
Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.
Check the trunk and branch
Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.
Check the combiner separately
Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.
Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.
Common questions
Does thicker trunk wire allow a 30 A Enphase IQ8 branch?
The modeled IQ8 series is listed for up to 20 A per branch. A larger upstream conductor can help with voltage rise within the listed branch design.
How many HMS-1600 units fit on a 30 A breaker?
The 240 V HMS-1600-4T-NA is rated at 6 A continuous per unit. With the listed 10 AWG trunk and sufficient adjusted ampacity, four units reach the 24 A continuous limit.