Worked example
13 × 1.23 A = 15.99 A continuous. With the 125% factor, that is 19.9875 A. Four equal branches total 63.96 A continuous and four 20 A handles total 80 A, both within the modeled IQ Combiner 5/5C limits.
Verify the exact part number and trunk configuration. One additional microinverter would increase both branch current and required overcurrent protection beyond the branch limit. Check array layout and voltage rise independently.
Calculation method
Use AC continuous current per microinverter
Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.
Check the trunk and branch
Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.
Check the combiner separately
Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.
Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.
Common questions
Does 13 IQ8+ units leave room for a fourteenth on a 20 A branch?
No. Fourteen units produce 17.22 A continuous, which exceeds the 16 A branch allowance.
How big is the four-branch output breaker floor in this IQ8+ example?
63.96 A × 1.25 = 79.95 A, giving an 80 A minimum standard sizing result before equipment and interconnection checks.