Worked example

11 × 1.35 = 14.85 A continuous, which becomes 18.5625 A at 125%. At 12 units, the continuous current reaches 16.2 A. Two compliant eleven-unit branches total 29.7 A continuous.

The 20 A branch limit and the breaker used for the combined output are separate. The minimum standard floor for two equal branches is 40 A. Confirm the combiner supports the branches and review the resulting source contribution at the bus.

Calculation method

  1. Use AC continuous current per microinverter

    Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.

  2. Check the trunk and branch

    Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.

  3. Check the combiner separately

    Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.

Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.

Common questions

Does 12 IQ8M fit the 20 A branch calculation?

At 1.35 A per unit, 12 produce 16.2 A continuous, beyond the 16 A budget.

Is the 325 VA IQ8M rating the same as its module DC wattage?

325 VA is the modeled AC continuous output rating. The compatible PV module range is specified separately.