Worked example
The 125% branch value is 19.9375 A. Three equal branches total 47.85 A continuous, yielding 59.8125 A for the combined output sizing floor and a 60 A standard breaker.
A larger proprietary trunk breaker is limited by product instructions. An installation can use appropriately sized upstream conductors to manage voltage rise where the equipment allows it. Verify the IQ8A regional SKU and compatible IQ cable.
Calculation method
Use AC continuous current per microinverter
Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.
Check the trunk and branch
Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.
Check the combiner separately
Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.
Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.
Common questions
How many IQ8A devices fit once cable ampacity is below 20 A?
If the adjusted trunk rating is below the selected 20 A breaker rating, that configuration is flagged. Check conductor sizing and the listed protection options.
Can the IQ8A voltage-rise model use the branch nameplate VA alone?
Use current and the actual conductor arrangement. For a distributed branch, voltage rise depends on where each inverter injects current.