Worked example
Two units draw 15.98 A continuous and require 19.975 A at 125%. Three units produce 23.97 A, requiring 29.9625 A. The prefilled three-unit, 20 A scenario exceeds the branch budget. Change the breaker, trunk and ampacity together to compare the listed 30 A case.
Use the continuous nameplate current and the manufacturer’s applicable trunk listing. The 208 V variant has a different current and unit limit, so the 240 V preset cannot be transferred to it.
Calculation method
Use AC continuous current per microinverter
Select the 240 V model, or enter its actual maximum continuous AC output current and listing limit. The DC module wattage serves a different purpose.
Check the trunk and branch
Divide the lower of the breaker and trunk ampacity by 1.25, then divide by the per-unit current and round down. Apply the manufacturer unit count and maximum breaker too.
Check the combiner separately
Add the branch continuous currents and multiply by 1.25 for an output breaker floor. The breaker sum at the combiner inputs and the system listing remain separate constraints.
Review the exact regional SKU and trunk compatibility, voltage rise to the grid, and the combiner and interconnection equipment listings. The worksheet assumes equal 240 V branches.
Common questions
Can three HMS-2000 units run on a 20 A breaker because each says 2 kVA peak?
Use 7.99 A per unit continuous at 240 V. Three units already exceed the branch’s 16 A continuous budget.
Does the 30 A HMS-2000 branch result apply at 208 V?
No. Use the separate 208 V rated output and the applicable data-sheet limits for that installation.