Worked example
A 200 A bus with a 200 A main has 40 A of 120% headroom. A 32 A inverter uses all 40 A after the 125% factor. If a simultaneous 16 A battery is added, the calculated total becomes 260 A.
Calculation method
Read the busbar and main separately
The panel label supplies the busbar rating. The protective device feeding the bus can be a different size. Multiply the bus rating by 1.20 to get the ceiling for this method.
Choose the input basis
The 2023 text uses 125% of the power-source output circuit current plus the main protective device. Using source breaker handles in place of their adjusted current values is a conservative screen when the devices cover the source load.
Confirm the layout
NEC 2023 places the opposite-end method in 705.12(B)(2), formerly 705.12(B)(3)(2) in 2020. The center-fed dwelling option is 705.12(B)(4) and uses one end of the bus.
Check the panel listing, Article 220 loads and the required label at the power source connection. Supply-side connections follow 705.11. An approved EMS or another 705.12 method needs its own documented design.
Common questions
What is the maximum PV breaker with a 225 A bus and 200 A main?
The conservative headroom is 70 A since 225 × 1.20 − 200 = 70, before subtracting storage or other source breakers.
Can the 120% result apply to a center-fed panel?
NEC 2023 705.12(B)(4) allows a center-fed dwelling panelboard with a source connection at one end when its conditions are met. Verify the panel listing and layout.