Worked example
200 × 1.20 = 240 A. The source contribution is 32 × 1.25 = 40 A. The main plus the source equals 240 A. A listed, appropriately located 40 A source breaker matches the modeled output requirement.
Read the actual label on the panel and trace where the main feeds the bus. Confirm the Article 220 load, the breaker listing, the required warning marking, and any applicable utility requirements. A battery that can export simultaneously changes the input.
Calculation method
Read the busbar and main separately
The panel label supplies the busbar rating. The protective device feeding the bus can be a different size. Multiply the bus rating by 1.20 to get the ceiling for this method.
Choose the input basis
The 2023 text uses 125% of the power-source output circuit current plus the main protective device. Using source breaker handles in place of their adjusted current values is a conservative screen when the devices cover the source load.
Confirm the layout
NEC 2023 places the opposite-end method in 705.12(B)(2), formerly 705.12(B)(3)(2) in 2020. The center-fed dwelling option is 705.12(B)(4) and uses one end of the bus.
Check the panel listing, Article 220 loads and the required label at the power source connection. Supply-side connections follow 705.11. An approved EMS or another 705.12 method needs its own documented design.
Common questions
What continuous inverter power fits the 40 A solar margin at 240 V?
32 A × 240 V is 7.68 kVA. Use the inverter maximum continuous AC rating and compare separately with utility and system limitations.
Can a 50 A source breaker be treated as a 40 A nameplate contribution?
The 2023 equation uses 125% of the circuit output current. The actual 50 A device still needs to satisfy breaker, conductor, equipment and marking requirements.