The 120% ceiling is 150 A. The conservative total is 100 + 40 + 15 = 155 A. With the 15 A battery breaker already counted, 35 A remains for a new standard PV breaker in this screening mode.
Try continuous output mode using both devices’ simultaneous nameplate output. If a documented energy-management system limits export, use its approved design and applicable code treatment. An operating preference in an app does not establish a listed current control.
Calculation method
Read the busbar and main separately
The panel label supplies the busbar rating. The protective device feeding the bus can be a different size. Multiply the bus rating by 1.20 to get the ceiling for this method.
Choose the input basis
The 2023 text uses 125% of the power-source output circuit current plus the main protective device. Using source breaker handles in place of their adjusted current values is a conservative screen when the devices cover the source load.
Confirm the layout
NEC 2023 places the opposite-end method in 705.12(B)(2), formerly 705.12(B)(3)(2) in 2020. The center-fed dwelling option is 705.12(B)(4) and uses one end of the bus.
Check the panel listing, Article 220 loads and the required label at the power source connection. Supply-side connections follow 705.11. An approved EMS or another 705.12 method needs its own documented design.
Common questions
Is a storage inverter counted when PV can export at the same time?
For this unmanaged case, add the simultaneous battery discharge contribution to PV. Confirm any documented operating limit under the applicable rules.
What happens if a battery never exports onto this bus?
Trace the backed-up and non-backed-up conductors and check system listing and controls. The interconnection arrangement determines which circuits count at this particular bus.