Worked example
The ceiling is 225 × 1.20 = 270 A. Subtracting the 200 A main leaves 70 A. A 56 A continuous PV output contributes exactly 70 A after the multiplier when storage is absent.
The main breaker handle alone cannot tell you the bus nameplate rating. Verify the label, eligible interconnection position, and whether this equipment has dedicated listing instructions for multiple sources. Check the schedule again if adding backup equipment.
Calculation method
Read the busbar and main separately
The panel label supplies the busbar rating. The protective device feeding the bus can be a different size. Multiply the bus rating by 1.20 to get the ceiling for this method.
Choose the input basis
The 2023 text uses 125% of the power-source output circuit current plus the main protective device. Using source breaker handles in place of their adjusted current values is a conservative screen when the devices cover the source load.
Confirm the layout
NEC 2023 places the opposite-end method in 705.12(B)(2), formerly 705.12(B)(3)(2) in 2020. The center-fed dwelling option is 705.12(B)(4) and uses one end of the bus.
Check the panel listing, Article 220 loads and the required label at the power source connection. Supply-side connections follow 705.11. An approved EMS or another 705.12 method needs its own documented design.
Common questions
What would a 225 A main do to the headroom on the same bus?
It leaves 45 A of 120% headroom instead of 70 A. Subtract other source contributions before choosing a PV rating.
Does 70 A of headroom establish utility export permission?
The panel calculation addresses busbar loading. Utility export and interconnection limits come from a separate review.